« on: July 13, 2010, 12:23:53 AM »
Reply with quote

i have a problem in using PLC, my project is control high voltage source to control temperatur furnace.
control temperatur using high voltage source. the problem is how to use special output of TM100D+1616(such as:PWM,PID control,ANALOG OUTPUT) that can handling this program.
i need to control temperatur at certain set point(SP), if temperatur less than SP then high voltage source must increase the voltage to increase temperatur furnace. otherwise, decrease the voltage to decrease temperatur.
nb: to control the high voltage source needs 0-12 V, that related to 0-2kV output of high voltage source.

regard
nugros
Report to moderator   Logged
support
Global Moderator
*****

Posts: 2729





View Profile WWW E-Mail
Re:output control
« Reply #1 on: July 13, 2010, 03:14:38 AM »
Reply with quote

It is possible to convert the 0-20mA analog output on the T100MD1616+ into 0-12V output if you connect the analog output to a 600 ohm resistor and ground. 20mA x 600 = 12V. So the output can be varied from 0V to 12V.

I am assuming that your high voltage output is electrically isolated from the PLC's low voltage circuit.
Report to moderator   Logged

Email: support@triplc.com
Tel: 1-877-TRI-PLCS
nugrozt
Newbie
*

Posts: 9



I'm a llama!

View Profile
Re:output control
« Reply #2 on: July 13, 2010, 05:25:47 AM »
Reply with quote

thanks.,

i need to  control 3 different high voltage source with the same output control, is it ok if i parallel 1 output PLC (0-12 V) to 3 different high voltage source?
Report to moderator   Logged
support
Global Moderator
*****

Posts: 2729





View Profile WWW E-Mail
Re:output control
« Reply #3 on: July 13, 2010, 09:50:49 AM »
Reply with quote

It depends on the impedance of the control input (0-12V) of your three loads. If these are high impedance inputs then it should be OK to connect the same output to all 3 of them in parallel.
Report to moderator   Logged

Email: support@triplc.com
Tel: 1-877-TRI-PLCS
nugrozt
Newbie
*

Posts: 9



I'm a llama!

View Profile
Re:output control
« Reply #4 on: July 29, 2010, 08:16:22 AM »
Reply with quote

i have problem with output DAC, i use the T-BASIC command SETDAC 1,2048 and connect a resistor (560 ohm) accross the output terminal D/A #1, when i measure the voltage between the resistor, it's just 4,7 V measured (in the manual book, it should have (560 ohm x 10mA= 5,6 V)?)
then, if i change output DAC with 4090,and the voltage measured is 4,9 V (why not 4,7 x 2 = 9,4 V)
was i wrong??
Report to moderator   Logged
support
Global Moderator
*****

Posts: 2729





View Profile WWW E-Mail
Re:output control
« Reply #5 on: July 29, 2010, 12:24:06 PM »
Reply with quote

Can you connect the DAC #1 output to a mA meter and check the output current when SETDAC 1,2048 and SETDAC 1,4090? What current did you get? You may have to calibrate the analog output current (there is a small preset next to the analog circuitry to calibrate the DAC).

Also you need to check if the analog voltage reference output 5V accurately? This is the voltage reference and if it is off then you need to turn the AVcc cal preset to get 5V.

If you can't get the 10mA or 20mA current after calibrating the AVcc reference the DAC preset then the DAC circuit may be damaged.
Report to moderator   Logged

Email: support@triplc.com
Tel: 1-877-TRI-PLCS
Pages: [1] Go Up Reply Notify of replies Send the topic Print 
? previous next ?
Jump to: 


Login with username, password and session length

Powered by MySQL Powered by PHP Internet PLC Forum | Powered by YaBB SE
© 2001-2004, YaBB SE Dev Team. All Rights Reserved.
Valid XHTML 1.0! Valid CSS!